In a private house      06/15/2019

Signal 20p specifications. TD Aktiv-SB: video surveillance and security systems. Technical parameters of the device

Description: Control and reception device (addressable loop expander) security and fire Signal-20P SMD, 20 loops, plastic housing.

Article: Signal-20P


Application area:

Key Features:

  • Programming AL types:
    • security
    • security entrance
    • anxious
    • technological

Specifications:

Parameter

Meaning

Signal-20P SMD

Number of alarm loops 20
Number of control programs for each output 37
Internal buffer capacity 64 events
Supply voltage 10.2 to 28 V
The current consumed by the device, in standby mode:
- with 24 V supply: 200 mA to 400 mA
- with 12 V supply: 300 mA to 600 mA
Loop load current 3 mA
Control of 5 outputs (output control logic is programmable):
- three relay outputs of the "dry contact" type for switching: with maximum voltage up to 28 V and current up to 2 A or up to 80 V and current from 0.1 mA to 50 mA (outputs "relay 1", "relay 2", "relay 3")
-two outputs with control of the health of the circuits for connecting annunciators: with maximum voltage up to 28 V and current up to 0.5 A (outputs "relay 4", "relay 5")
Working temperature range -30 to +55°C
dimensions 230 x 135 x 43 mm

The Signal-20P device is available in two types of cases: metal and plastic. Programming and control is carried out by the S2000 remote control or from a computer using specialized software. Signal-20P can be used both in stand-alone mode and as part of the Orion AWS. The device can be powered by 12V or 24V voltage sources. The main and backup power supply can be used, and the failure of the power supply line of one of the sources (short circuit or open circuit) does not affect the operation of the other. Signal-20P has a programmable control logic for five relays, which allows you to have 37 control programs for each output.

Application area:

  • Autonomous work and work as a part of ISO "Orion"

Key Features:

  • 20 alarm loops with all types of security and fire detectors
  • Two power inputs: for connecting the main and backup power sources, voltage from 12 V to 24 V. A failure of the power supply line of one of the sources (short circuit or open circuit) does not affect the operation of the other
  • Control of output circuits "relay 4" and "relay 5", intended for connection of external annunciators, for breakage and short circuit
  • Programming AL types:
    • fire smoke two-threshold (with recognition of the operation of one and two detectors in the loop)
    • fire combined one-threshold (with the ability to connect thermal and smoke detectors)
    • fire thermal two-threshold
    • security
    • security with detection of violation of the blocking contact of the detector
    • security entrance
    • anxious
    • technological
    • programmable technological
  • The ability to measure the loop resistance and transfer its value to the "S2000" console or "Orion" workstation
  • Operability in case of violation of the RS-485 interface and after its restoration, transmission to the "S2000" or "Orion" workstations of accumulated messages with the time of their occurrence
  • Connecting the key reader "Dallas Touch Memory" allows you to centrally manage (take, remove) partitions and identify the household
  • Programmable control logic for five relays (37 local control tactics)

Signal-20P SMD control of 20 loops, the ability to program the parameters of each loop for operation in the security or fire alarm, fixation of alarms in each loop of one and two fire detectors, fire extinguishing control outputs, control from built-in switches or via RS-485 interface from the S2000 remote control or PC.

Buying Signal-20P SMD in the specialized Jet-Video Company, you can order fast free delivery of high-quality licensed equipment by affordable prices.

Key Features Signal-20P SMD:

  • 20 alarm loops with all types of security and fire detectors
  • Two power inputs: for connecting the main and backup power sources, voltage from 12 V to 24 V. A failure of the power supply line of one of the sources (short circuit or open circuit) does not affect the operation of the other
  • Control of output circuits "relay 4" and "relay 5", intended for connection of external annunciators, for breakage and short circuit
  • Programming AL types:
    fire smoke two-threshold (with recognition of the operation of one and two detectors in the loop)
    fire combined single-threshold (with the ability to connect heat and smoke detectors)
    fire thermal two-threshold
    security
    security with detection of violation of the blocking contact of the detector
    security entrance
    anxious
    technological
    programmable technological
  • The ability to measure the loop resistance and transfer its value to the "S2000" console or "Orion" workstation
  • Operability in case of violation of the RS-485 interface and after its restoration, transmission to the "S2000" or "Orion" workstations of accumulated messages with the time of their occurrence
  • Connecting the key reader "Dallas Touch Memory" allows you to centrally manage (take, remove) partitions and identify the household
  • Programmable control logic for five relays (37 local control tactics)

You can be sure of the quality Signal-20P SMD. All equipment stocked by Jet-Video is covered by a manufacturer's warranty. We are glad that you contacted us to buy Signal-20P SMD We will try to make the selling process as pleasant as possible!

Specifications Signal-20P SMD:

  • Number of alarm loops - 20
  • Number of control programs for each output - 37
  • Internal buffer capacity - 64 events
  • Supply voltage - from 10.2 to 28 V
  • Current consumption of the device, in standby mode: with 24 V supply: from 200 mA to 400 mA, with 12 V supply: from 300 mA to 600 mA
  • Loop load current - 3 mA
  • Management of 5 relay outputs
    three relay outputs of the "dry contact" type for switching: with a maximum voltage of up to 28 V and a current of up to 2 A or up to 80 V and a current of 0.1 mA to 50 mA (outputs "relay 1", "relay 2", "relay 3"); two outputs with control of the health of the sirens connection circuits: with a maximum voltage of up to 28 V and a current of up to 0.5 A (outputs "relay 4", "relay 5");
  • Working temperature range - from minus 30 to +50 °С
  • Dimensions: 230 x 135 x 43 mm

According to the instructions, "Signal-20P SMD" was developed and put into operation for operation in fire, alarm and security alarm systems. The control fire and security device can be equipped with 20 communication lines in the system. The composition includes all types of fire and security equipment for detecting and informing about the occurrence of fires or violations of the protected perimeter.

general description

In the description of the instruction "Signal-20P SMD" the device is listed as a device with control and reception functions in security and fire system. It has technological capabilities to control up to 20 areas. It receives information from warning devices that have automatic, manual or active mode. It has control over sound and light technical means of detecting and generating a fire signal. Functioning in the RS-485 software shell, it receives commands and issues information to the network controller. Such control points, according to the instructions of "Signal-20P SMD", can be control panels of the S2000 modification or a personal computer with installed on it software Orion type.

The device broadcasts alerts "fire" and "malfunction" to the fire station control panel. receives alarm notifications from this device. Interacts with Touch Memory electronic identifiers.

Purpose of the device

According to the instructions of "Signal-20P SMD", the purpose of the control device is to subordinate to its functionality the processes of arming and disarming single alarm loops. Also, the device can perform these tasks with a group of loops, it depends on the orders of the network controller.

"Signal-20P SMD" monitors breaks and short circuits on lines to which signal annunciators are connected. The device provides connection alternative source power supply to the auxiliary input. Sends the electronic ID cipher to the network controller for organized management sections. All necessary information according to the state of the partition is displayed on an external indicator built into the device (according to the instructions "Signal-20P SMD").

The operation of the device is defined as addressable and only in a joint group with the Orion security system.

The device "Signal-20P SMD" is designed to protect premises and structures from fires and unauthorized access. Such objects most often become various offices of enterprises and companies, commercial buildings, banking institutions, storage areas, residential buildings and similar covered buildings. building construction.

System operating conditions

The instruction manual for "Signal-20P SMD" recommends taking care of the device and puts forward a number of requirements for working with it.

The device must only be installed inside buildings. closed type with no heating. The power supply is specially reserved for uninterrupted operation, or there must be two of them - the main and the alternative. Required voltage varies from 10 to 28 V. It is recommended to use power supplies model range"Rip" company "Bolid". It is strictly not recommended by the manufacturer to use the Signal-20P SMD device in dusty rooms, in explosive environments and in conditions where negative environmental factors can affect the device.

Proper performance is ensured by the device in conditions at an ambient temperature of -30 ℃ to +50 ℃, air humidity should not exceed 98% at +25 ℃. Vibration pressure should be in the range from 1 to 35 Hz. If the electromagnetic environment is not suitable, the quality of the operating functions is not guaranteed by the manufacturer.

Technical parameters of the device

According to the instructions, "Signal-20P SMD" can process the information volume of 20 signal loops. Serves up to five switched circuits, the number of control circuit inputs is 26. This number includes 20 fire alarm loops, an electronic identifier circuit, two circuits of the RS-485 interface shell, controlled circuits of the outputs of two relays and inputs of the electrical power supply of the device.

"Signal-20P SMD" has 7 outlets. They are defined as 3 relay outputs for switching with a voltage of 28 V and a current of up to 2 A, 2 control outputs for connection technical means fire detection and signaling, two outputs that control an external indicator for scanning an electronic ID.

Informativeness of the system

The device notifies about such events as:

  • arming the loop trunks or an unsuccessful attempt;
  • triggering of sensors;
  • fire or prerequisites for its occurrence;
  • breaks in loops and circuits;
  • short circuits of own circuits;
  • violation of the integrity of the body;
  • restoration of the last and output circuits;
  • test run;
  • removal of loops from protection;
  • device reset;
  • reset alarms;
  • breakdown and restoration of power sources;
  • interruption and restoration of the technological signal loop;
  • quiet anxiety;
  • entrance area alarms;
  • restoration or violation of a loop disconnected from the security system;
  • unauthorized entry alarm.

The difference between "Signal-20P" and "Signal-20P version 01" is in the material and size of the case.

Designed for use as part of ISO "Orion" for control various types security and fire conventional detectors, contactors and signaling devices with normally closed or normally open contacts and relay control of external actuators.

Description:

  • Up to 20 radial alarm loops
  • Programmable selection of the type of alarm loops:
    • type 1: fire smoke double threshold
    • type 2: fire combined single-threshold (with the ability to connect heat and smoke detectors)
    • type 3: fire thermal two-threshold (with recognition of the operation of one and two detectors in the loop)
    • type 4: security
    • type 5: security with detection of a violation of the blocking contact of the detector
    • type 6: technological
    • type 7: burglar input
    • type 11: alarming
    • type 12: programmable process
    • type 16: fireman manual
    • type 17: water signal
    • type 18: fire launcher
  • Arming/disarming control of alarm loops, output relays of the device via RS-485 interface from the control panel or ISO "Orion" keypads
  • Connecting a key reader "Touch Memory" for user identification and partition management (taking, removing)
  • Programmable outputs (37 local control tactics)
  • Monitoring of two outputs for open and short circuit
  • Two power inputs: for connecting the main and backup power supplies

Specifications:

PARAMETER NAME

PARAMETER VALUE

Number of radial conventional signaling loops (AL)

Max. AL wire resistance without taking into account the termination resistance

1 kOhm for security loops
100 ohm for fire loops

Permissible leakage resistance between loop wires or each wire and ground

20 kOhm for security loops
50 kOhm for fire alarms

Devices connected to the loop

Conventional security and fire detectors with relay output

No limits

Non-address security detectors powered by AL

with total current consumption up to 3 mA

Non-address fire detectors powered by AL

with a total current consumption of up to 3 mA (with a total current consumption of up to 1.2 mA with simultaneous activation of heat and smoke detectors)

Voltage at each AL input

19 V ÷ 24 V with the installation of a terminating resistor 4.7 kOhm ± 5% and the current consumption of the detectors 0 ÷ 3 mA,
27 ± 0.5 V with loop break

Current limitation in a short-circuited loop

26.5 mA (no more than 20 mA through a triggered detector, when the detector voltage is more than 6.8 V)

Light indication

1 mode display indicator

Built-in buzzer

Tamper sensor

microcontact

Non-volatile event buffer

4096 messages

Interface

RS-485, protocol "Orion", "Orion 2.1"

Unit power

from external source direct current

Supply voltage

10.2 ÷ 28.0 VDC

Number of power inputs

Current consumption

in standby mode (depends on the number of current-consuming detectors in the loop)

200 - 300 mA at 24 V supply voltage
400 - 600 mA at 12 V supply voltage

in fire mode

330 mA at 24 V supply voltage
650 mA at 12 V supply voltage

Ready for operation after power on

no more than 3 s

External reader of electronic identifiers (EI)

Connected reader interface

Dallas Touch Memory, iButton

Reader LED control

Two LEDs (green and red). Control signal "+5V CMOS" with current limitation with direct connection of LEDs at the level of 10 mA

Reader buzzer control

Electromagnetic relays (dry contact)

3 pcs.:
28 V - up to 2 A or
80 V - 0.1 mA to 50 mA

Electromagnetic relays

2 pcs.:
2 pcs.: 12 or 24 V (determined by the supply voltage of the device), up to 0.8 A, with monitoring of the load connection circuits for open and short circuits, (monitoring current 1.5 mA), overcurrent protection

Working temperature range

-30 to +50 °C

Relative Humidity

up to 98% at +25 °C

Case protection degree

Housing material

"Signal-20P version 01"

"Signal-20P"

dimensions

"Signal-20P version 01"

229x136x41 mm

"Signal-20P"

Block weight

"Signal-20P version 01"

no more than 0.8 kg

The activity of our video surveillance online store covers the entire range of security and protection equipment, which includes:

and much more

Carrying out deliveries throughout Russia, our company delivers goods even to the most remote regions of the country. We try to satisfy the most demanding client.

Active-SB specialists understand the specifics of the work of security and video surveillance systems not only in Moscow, but also in remote regions with difficult climatic conditions. Our employees will offer you the most suitable options both in terms of functionality and cost, tell you about their capabilities and justify the need to use certain technical systems.
Trading House of Security Systems Aktiv-SB carries out service and warranty maintenance of the equipment sold, acceptance and inspection of goods of inadequate quality, and exchange of faulty equipment.

Our clients are commercial organizations and end users, assembly companies and state enterprises. More than 50,000 registered users of the corporate website have access to a constantly updated database of technical documentation, certificates for modern systems security, as well as participate in the affiliate program and special promotions held by the company.

For the convenience of our relationship with customers, we cooperate with installation organizations that are ready to install video surveillance systems of any complexity and will always come to your aid. Therefore, if necessary, you can not only purchase equipment from us, but also, for example, order the installation of video surveillance systems or conduct Maintenance other security systems.

The work of our hypermarket of security systems is based on the principles of honesty, openness and decency. We look to the future with confidence, strive to develop and improve every day.